HONEYWELL EG1033AC01 EG Flame Amplifier (LG Series).Honeywell EG1033AC01 UV Flame Monitoring System provides superior flameout protection in industrial gas turbines for use in industrial power generation gas turbine installations and more. The system detects UV radiation from hydrocarbon flames and outputs a signal with or without a flame, and has more than 35 years of reliable performance on General Electric (and licensee) gas turbines in applications such as power generation, pumping stations, shipboard power generation, and more, with a wide range of sensors, amplifier types, and cable lengths available.
To learn more about this product click on the file below or download the file:
HONEYWELL EG1033AC01 EG Flame Amplifier (LG Series).pdf
EG1033AC/AD Features:
Physical dimensions are 6.62 x 4.25 x 4.44 inches with four 0.20 inch diameter mounting holes spaced 6.00 x 2.00 inches apart.
Power input is 20 - 35Vdc, 10 watts maximum.
The amplifier output is a relay contact.
Flame detection time 0.1 seconds typical, 1.0 seconds maximum, flame loss detection time 0.2 seconds maximum.
Complies with CE marking related directives (EMC Directive 89/336/EEC, LVD Directive 73/23/EEC).
Each amplifier can power two sensors, single or dual applications, and provide a separate output signal for each sensor, EG1033AD models differ in chassis ground shield connection versus input power supply low potential connection.
HONEYWELL EG1033AC01 EG Flame Amplifier Related Products:
ABB UNIROL1010 3BHE035301R0001 Brushless excitation
ABB PP D113 B03-19-150000 3BHE023584R1923 AC 800PEC controller
FOXBORO RH924WA fiber adapters for FCP280
BENTLY 3500/91M 190782-01 EGD Communication Gateway Module